HPE Metered Power Distribution Units (PDU): технические характеристики и документация
В архивеOverview
|
HPE Metered Power Distribution Units (PDU) | |
|
HPE Metered Power Distribution Units (PDU) provide rack level power monitoring over the network. With billing grade accuracy these PDUs are excellent choices for data centers wanting to make the most of circuit capacity or for co-location facilities needing to precisely track power usage for billing purposes. | |
|
| |
|
|
|
|
1UModels (D9N46A shown) |
Half Height Models (D9N45A shown) |
|
|
|
|
Mid Height Models (D9N47A/D9N48A shown) |
Full Height Models (D9N58A/D9N59A shown) |
Models
|
Vertical PDU Models |
|
|
Single Phase, Half Height (22U) |
|
|
HPE Metered 4.9kVA/L6-30P 24A/208V Outlets (12) C13/Vertical NA/JP PDU |
G9Z05A |
|
HPE Metered 7.3kVA/60309 3-wire 32A/230V Outlets (12) C13/Vertical INTL PDU |
G9Z06A |
|
Three Phase, Half Height (22U) |
|
|
HPE Metered 3.6kVA/60320 C20 Detachable 16A/230V Outlets (16) C13/Vertical WW PDU |
D9N45A |
|
Single Phase, Mid Height (36U) |
|
|
HPE Metered 4.9kVA/L6-30P 24A/208V Outlets (20) C13 (4) C19/Vertical NA/JP PDU |
D9N47A |
|
HPE Metered 7.3kVA/60309 32A 3-wire/230V Outlets (20) C13 (4) C19/Vertical INTL PDU |
D9N48A |
|
Three Phase, Mid Height (36U) |
|
|
HPE Metered 3Ph 5.7kVA/L21-20P 16A/120-208V Outlets (13) C13 (3)5-20R/Vertical NA/JP PDU |
D9N52A |
|
HPE Metered 3Ph 8.6kVA/L21-30P 24A/120-208V Outlets (18) C13 (3) C19 (3) 5-20R/Vertical NA/JP PDU |
D9N53A |
|
HPE Metered 3Ph 8.6kVA/L15-30P 24A/208V Outlets (18) C13 (3) C19/Vertical NA/JP PDU |
D9N51A |
|
HPE Metered 3Ph 11kVA/60309 5-wire 16A/230V Outlets (18) C13 (3) C19/Vertical INTL PDU |
D9N55A |
|
Single Phase, Full Height (42U) |
|
|
HPE Metered 7.3kVA/60309 32A 3-wire/230V Outlets (32) C13 (4) C19/Vertical INTL PDU |
D9N50A |
|
HPE Metered 8.3kVA/CS8265C 40A/208V Outlets (30) C13 (3) C19/Vertical NA PDU |
D9N49A |
|
Three Phase, Full Height (42U) |
|
|
HPE Metered 3Ph 19.9kVA/L22-30P 24A/277V Outlets (30) RF-203P-HP/Vertical NA PDU |
D9N63A |
|
HPE Metered 3Ph 11kVA/60309 5-wire 16A/230V Outlets (30) C13 (3) C19/Vertical INTL PDU |
D9N57A |
|
HPE Metered 3Ph 16.6kVA/60309 32A-30A 5-wire 24A/230V Outlets (30) C13 (3) C19/Vertical NA/JP PDU |
D9N61A |
|
HPE Metered 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (24) C13 (3) C19/Vertical NA/JP PDU |
D9N54A |
|
HPE Metered 3Ph 22kVA/60309 5-wire 32A/230V Outlets (30) C13 (3) C19/Vertical INTL PDU |
D9N56A |
|
HPE Metered 3Ph 14.4kVA/CS8365C 40A/208V Outlets (12) C13 (12) C19/Vertical NA/JP PDU |
D9N58A |
|
HPE Metered 3Ph 16.6kVA/60309 32A-30A 5-wire 24A/230V Outlets (12) C13 (12) C19/Vertical NA/JP PDU |
D9N62A |
|
HPE Metered 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (12) C13 (12) C19/Vertical NA/JP PDU |
D9N59A |
|
HPE Metered 3Ph 17.3kVA/60309 60A 4-wire WT 48A/208V Outlets (12) C13 (12) C19/Vertical NA/JP PDU |
G9Z07A |
|
HPE Metered 3Ph 22kVA/60309 5-wire 32A/230V Outlets (12) C13 (12) C19/Vertical INTL PDU |
D9N60A |
|
HPE Metered 3Ph 22kVA/60309 5-wire WT 32A/230V Outlets (12) C13 (12) C19/Vertical INTL PDU |
G9Z08A |
|
Horizontal PDU Models |
|
|
Single Phase, 1U |
|
|
HPE Metered 2.8kVA/L5-30P 24A/120V Outlets (12) 5-20R/Horizontal NA/JP PDU |
D9N43A |
|
HPE Metered 3.6kVA/60320 C20 Detachable 16A/230V Outlets (12) C13/Horizontal WW PDU |
D9N46A |
|
HPE Metered 4.9kVA/L6-30P 24A/208V Outlets (12) C13/Horizontal NA/JP PDU |
D9N44A |
Standard Features
|
Key Features List |
|
|
| |
|
Billing grade accuracy |
All HPE Metered PDUs meet IEC 62053-21, Class 1 standards for ±1% or better accuracy in power monitoring of:
Accurate inlet and load segment power monitoring improves circuit utilization and provide information that can help balance power throughout the data center to maximize efficiency and cooling. A LCD screen on the HPE Metered PDU provides local monitoring and local alert indications. |
|
| |
|
Flexible Software |
|
|
| |
|
Multiple models for flexible installation |
The HPE Metered PDUs are available in four form factors for a variety of racks and environments. All HPE Metered PDUs can be mounted to stay completely out of the critical rear maintenance path needed to service IT equipment in the rack. All vertical models use industry standard button and keyhole mounting for simple drop in installation in HPE Advanced and Enterprise Series racks and many third party racks.
NOTE: Facing the outlets into the rack will interfere with the lower few rack U spaces of the rear maintenance zone due to breakers on the PDUs. |
|
| |
|
Vertical PDU Form Factors |
NOTE: When mounted in the standard rear facing configuration only 1 Mid or Full Height PDU can be mounted per side of the rack. Up to 2 Half Height PDUs can be mounted per side in the standard rear facing configuration in a 42U or taller rack. |
|
| |
|
Environmental monitoring |
An optional environmental sensor attaches to the HPE Metered PDU and can measure air temperature and humidity in the front or rear of the rack. The environmental senor will send alerts over the network based on user defined thresholds. |
|
| |
|
Easy Installation and compatibility |
Standard button and keyhole mounting provides simple drop in installation in HPE Advanced Series racks, Enterprise Series Racks, and many third party racks. |
|
| |
|
Warranty |
HPE Metered PDUs are backed by a limited 3-year warranty. |
Service and Support
|
HPE Support Services |
Support services provide a range of life cycle support options that let you choose the service levels that meet your business requirements, from basic to mission-critical.
NOTE: For more information on Hewlett Packard Enterprise support services, contact any of our worldwide sales offices or resellers or visit our worldwide Web site on the internet at: http://www.hp.com/hps/carepack |
Related Options
|
HPE Environmental Sensor for Remote Monitoring PDUs |
HP Environmental Sensor for Remote Monitored and Managed PDUs |
E2D53A |
|
| |
|
NOTE: The HPE Environmental Sensor comes with a 6 foot RJ45-RJ45 cable and can be mounted in various locations within the rack using the supplied Velcro strips or mounting screw. RJ45 cables up to 30 feet (9.1m) long may be used. |
| |
|
| ||
|
HPE Country specific C19 PDU Inlet Cords for D9N45A and D9N46A |
HP C19 - Nema L6-20P NA/JP 250V 20Amp High Voltage 3.6m Power Cord |
AF593A |
|
HP C19 - NBR-14136 BR 250V 16Amp 2.5m Power Cord |
AF592A | |
|
HP C19 - GB-1002 CN 250V 16Amp 2.5m Power Cord |
AF584A | |
|
HP C19 - IS-1293 IN/PK/BD 250V 16Amp 2.5m Power Cord |
AF582A | |
|
HP C19 - ISI-32 IL 250V 16Amp 2.5m Power Cord |
AF583A | |
|
HP C19 - AS3112-3 AU/NZ 250V 15Amp 3.6m Power Cord |
AF577A | |
|
HP C19 - IEC-309 DK/SE/AR 250V 16Amp 3.6m Power Cord |
AF581A | |
|
HP C19 - CEE-VII EU 250V 16Amp 3.6m Power Cord |
AF576A | |
|
HP C19 - CEI-23-50 IT/CL 250V 16Amp 3.6m Power Cord |
AF580A | |
|
HP C19 - SABS-164 ZA 250V 16Amp 3.6m Power Cord |
AF579A | |
|
HP C19 - BS-1363/A UK/HK/SG 250V 13Amp 3.6m Power Cord |
359615-031 | |
|
HP 240 VAC 4.5M Unterminated End NA Power Cord |
E7806A | |
|
| ||
|
HPE Jumper Cables |
HP C13 - C14 WW 250V 10A Gray 0.7m Jumper Cord |
A0K03A |
|
HP C13 - C14 WW 250V 10Amp 0.7m Jumper Cord |
142257-B28 | |
|
HP C13 - C14 WW 250V 10Amp 1.4m Jumper Cord |
142257-006 | |
|
HP C13 - C14 WW 250V 10A Gray 1.37m Jumper Cord |
A0K04A | |
|
HP C13 - C14 WW 250V 10Amp 1.4m 15 pc Jumper Cord |
142257-007 | |
|
HP C13 - C14 WW 250V 10Amp 2.0m Jumper Cord |
A0K02A | |
|
HP C13 - C14 WW 250V 10Amp Flint Gray 2.0m Jumper Cord |
AF573A | |
|
HP C13 - C14 WW 250V 10Amp 2.5m Jumper Cord |
142257-002 | |
|
HP C13 - C14 WW 250V 10Amp 3.0m Jumper Cord |
142257-003 | |
|
HP C13 - C14 WW 250V 10A Gray 3.0m Jumper Cord |
A0K06A | |
|
HP C20 - C13 WW 250V 15Amp 2.0m Jumper Cord |
AF590A | |
|
HP C19 - C20 WW 250V 16Amp Flint Gray 1.20m Jumper Cord |
AF575A | |
|
HP C19 - C20 WW 250V 16Amp Flint Gray 2.0m Jumper Cord |
AF574A | |
|
HP C19 - C20 WW 250V 16Amp 2.5m Jumper Cord |
295633-B22 | |
|
HP 200-250V 10A C15 to C14 .76m Jumper Cable |
E7807A | |
|
| ||
|
HPE Mounting Brackets |
HP Vertical PDU 10K G2 Mounting Kit |
H6L32A |
|
NOTE: Allows HPE Basic and Remote Monitoring PDU vertical models to be mounted in HPE 10000 G2 series racks and in the HPE Basic Series rack. This bracket is not needed for mounting in the HPE Advanced or Enterprise Series racks. PDUs may interfere with the rear maintenance zone when using these brackets. |
| |
|
| ||
|
HPE 277 Volt options for D9N63A |
HP LS-26 to LS-25 277 Volt 15Amp AC 0.76m Jumper Cord |
TK801A |
|
HP LS-26 to LS-25 277 Volt 15Amp AC 1.37M Jumper Cord |
TK802A | |
|
HP 800VA - 277V Input / 230V Output NA Rack Mount Transformer |
H3X09A | |
|
NOTE: 720 watt, 2U transformer converts 277V to 230V for up to 4 devices. |
| |
|
HPE LS26 to LS-25 jumper cables are compatible with the following 94% efficient HPE Common Slot power supplies |
| |
|
HP 500W Common Slot 277VAC Hot Plug Power Supply Kit |
717362-B21 | |
|
HP 750W Common Slot 277VAC Hot Plug Power Supply Kit |
717364-B21 | |
|
HP 1200W Common Slot 277VAC Hot Plug Power Supply Kit |
717359-B21 |
Model Selection Matrix
|
1U Horizontal Models | |||||||
|
Model |
Part Number |
Input Circuit |
Current Maximum |
Load capacity |
Input Connection |
Output circuit breakers |
Outlet Connections |
|
2.8kVA PDU |
D9N43A |
100-120V |
24A |
2880VA |
8ft(2.4m) cord with attached NEMA L5-30P |
2 x 20A |
12 x NEMA 5-20R |
|
3.6kVA PDU |
D9N46A |
200-240V |
16A |
3680VA |
Detachable input power cord with an IEC 320-C20 inlet on PDU* |
n/a |
12 x IEC C13 |
|
4.9kVA PDU |
D9N44A |
200-240V |
24A |
4992VA @208V |
8ft(2.4m) cord with attached NEMA L6-30P |
2 x 20A |
12 x IEC C13 |
|
Half Height Vertical Models | |||||||
|
Model |
Part Number |
Input Voltage |
Current Maximum |
Load capacity |
Input Connection |
Output circuit breaker |
Outlet Connections |
|
3.6kVA PDU |
D9N45A |
200-240V |
16A |
3680VA |
Detachable input power cord with an IEC 320-C20 inlet on PDU* |
n/a |
16 x IEC C13 |
|
4.9kVA PDU |
G9Z05A |
200-240V 30A |
24A |
4992VA @208V |
10ft(3m) cord with attached NEMA L6-30P |
2 x 20A |
12 x IEC C13 |
|
7.3kVA PDU |
G9Z06A |
200-240V 32A |
32A |
7360VA @230V |
10ft(3m) cord with attached IEC 332P6 |
2 x 16A |
12 x IEC C13 |
|
Mid Height Vertical Models | |||||||
|
Model |
Part Number |
Input Voltage |
Current Maximum |
Load capacity |
Input Connection |
Output circuit breaker |
Outlet Connections |
|
4.9kVA PDU |
D9N47A |
200-240V |
24A |
4992VA @208V |
8ft(2.4m) cord with attached NEMA L6-30P |
2 x 20A |
20 x IEC C13 |
|
7.3kVA PDU |
D9N48A |
200-240V |
32A |
7360VA @230V |
8ft(2.4m) cord with attached IEC 332P6 |
2 x 16A |
20 x IEC C13 |
|
5.7kVA Dual Voltage PDU |
D9N52A |
200-208V |
27.7A |
5764VA @208V |
8ft(2.4m) cord with attached NEMA L21-20P |
n/a |
18 x IEC C13 |
|
8.6kVA Dual Voltage PDU |
D9N53A |
200-208V |
41.5A |
8646VA @208V |
8ft(2.4m) cord with attached NEMA L21-30P |
3 x 20A |
18 x IEC C13 |
|
8.6kVA PDU |
D9N51A |
200-208V |
41.5A |
8646VA @208V |
8ft(2.4m) cord with attached NEMA 15-30P |
3 x 20A |
18 x IEC C13 |
|
11kVA PDU |
D9N55A |
380-415V |
16A/phase |
11040VA |
8ft(2.4m) cord with attached IEC 516P6 |
n/a |
18 x IEC C13 |
|
Full Height Vertical Models | |||||||
|
Model |
Part Number |
Input Voltage |
Current Maximum |
Load capacity |
Input Connection |
Output circuit breaker |
Outlet Connections |
|
7.3kVA PDU |
D9N50A |
200-240V |
32A |
7360VA @230V |
8ft(2.4m) cord with attached |
2 x 16A |
32 x IEC C13 |
|
8.3kVA PDU |
D9N49A |
200-240V |
40A |
8320VA @208V |
8ft(2.4m) cord with attached CS8265C |
3 x 20A |
30 x IEC C13 |
|
11kVA PDU |
D9N57A |
380-415V |
16A/phase |
11040VA |
8ft(2.4m) cord with attached |
n/a |
30 x IEC C13 |
|
16.6kVA PDU |
D9N61A |
380-415V |
24A/phase |
16560VA @ 400V 3 Phase |
8ft(2.4m) cord with attached |
6 x 20A |
30 x IEC C13 |
|
17.3kVA PDU |
D9N54A |
200-208V |
83.04A |
17292VA @ 208V 3 Phase |
8ft(2.4m) cord with attached |
6 x 20A |
24 x IEC C13 |
|
22kVA PDU |
D9N56A |
380-415V |
32A/phase |
22080VA @ 400V 3 Phase |
8ft(2.4m) cord with attached |
6 x16A |
30 x IEC C13 |
|
14.4kVA PDU |
D9N58A |
200-208V |
69.28A |
14410VA @ 208V 3 Phase |
8ft(2.4m) cord with attached CS8365C |
6 x 20A |
12 x IEC C13 |
|
16.6kVA PDU |
D9N62A |
380-415V |
24A/phase |
16560VA @ 400V 3 Phase |
8ft(2.4m) cord with attached |
6 x 20A |
12 x IEC C13 |
|
17.3kVA PDU |
D9N59A |
200-208V |
83.04A |
17292VA @ 208V 3 Phase |
8ft(2.4m) cord with attached |
6 x 20A |
12 x IEC C13 |
|
17.3kVA PDU |
G9Z07A |
200-208V |
83.04A |
17292VA @ 208V 3 Phase |
10ft(3m) cord with attached |
6 x 20A |
12 x IEC C13 |
|
22kVA PDU |
D9N60A |
380-415V |
32A/phase |
22080VA @ 400V 3 Phase |
8ft(2.4m) cord with attached |
6 x16A |
12 x IEC C13 |
|
22kVA PDU |
G9Z08A |
380-415V |
32A/phase |
22080VA @ 400V 3 Phase |
10ft(3m) cord with attached IP67 Watertight |
6 x16A |
12 x IEC C13 |
|
480/277 Volt Model | |||||||
|
19.9kVA PDU |
D9N63A |
480V 30A 3 Phase WYE |
24A /phase |
19944VA @480V 3 Phase |
8ft(2.4M) cord with attached NEMA L22-30P |
6 x 20A |
30 x RF203P-HPE |
|
| |||||||
|
* HPE Metered PDU models D9N45A and D9N46A require an IEC 320-C19 to country specific plug inlet cord which is sold separately. | |||||||
|
Disclaimer: HPE makes no recommendations regarding power connector manufactures. Please consult a licensed professional to determine the best connector or receptacle for your specific needs. | |||||||
|
Voltage |
Amps |
# Wires |
Plug Name |
Sample Plug Image | |
|
100-125 V Single Phase |
20 A |
3 |
NEMA L5-20P |
|
|
|
30 A |
3 |
NEMA L5-30P |
|
| |
|
200-240 V Single Phase |
20 A |
3 |
IEC C20 |
|
|
|
20 A |
3 |
NEMA L6-20P |
|
| |
|
30 A |
3 |
NEMA L6-30P |
|
| |
|
32 A |
3 |
IEC 309 32A, 2Pole, 3Wire |
|
| |
|
20 A |
5 |
NEMA L21-20P |
|
| |
|
208 V Three Phase
|
16 A |
5 |
IEC 309 16 A, 3Pole, 5Wire |
|
|
|
30 A |
5 |
NEMA L21-30P |
|
| |
|
50 A |
4 |
CS8365C |
|
| |
|
60 A |
4 |
IEC 309 60A, 3Pole, 4Wire |
|
| |
|
400 - 415 V Three Phase |
32 A |
5 |
IEC 309 32 A, 3Pole, 5Wire |
|
|
Technical Specifications
|
All PDUs |
|
|
Operating Temperature (INTL and WW models) |
50° to 122° F (10° to 50° C) |
|
Operating Relative Humidity (%) |
10% to 90% |
|
Operating Elevation |
0 to 10,000 ft (0 to 3048 m) |
|
Storage Temperature |
-4° to 140° F (-20° to 60° C) |
|
Storage Relative Humidity (%) |
5% to 95% |
|
Storage Elevation |
0 to 30,000 ft (0 to 9144 m) |
|
Input Plug Length (D9NxxA attached cord units) |
96 inches (243.8 cm) |
|
Input Plug Length (G9Z07A and G9Z08A) |
120 inches (304.8 cm) |
|
Conformance Standards |
UL, CUL, VCCI - NA/JPN models |
|
Mechanical Dimensions (WxHxD) - 1U models |
17.25 x 1.71 x 6.16 in (43.8 x 4.34 x 15.65 cm) |
|
Mechanical Dimensions (WxHxD) - Half Height models |
2.05 x 30 x 2.05 (5.2 x 76.2 x 5.2 cm) |
|
Mechanical Dimensions (WxHxD) - Mid Height models |
2.05 x 56.12 x 2.05in (5.2 x 142.54 x 5.2 cm) |
|
Mechanical Dimensions (WxHxD) - Full Height models |
2.05 x 66.59 x2.05 in (5.2 x 169.14 x5.2) |
|
Kit Contents - All Remote Monitoring PDUs |
All models ship with:
|
|
| |
|
Environment-friendly Products and Approach |
End-of-life Management and Recycling |
Hewlett Packard Enterprise offers end-of-life Hewlett Packard Enterprise product return, trade-in, and recycling programs in many geographic areas. For trade-in information, please go to: http://www.hp.com/go/green. To recycle your product, please go to: http://www.hp.com/go/green or contact your nearest Hewlett Packard Enterprise sales office. Products returned to Hewlett Packard Enterprise will be recycled, recovered or disposed of in a responsible manner. |
Summary of Changes
|
Date |
Version History |
Action |
Description of Change | ||||||||||||||
|
16-Feb-2016 |
From Version 9 to10 |
Changed |
Overview, Models, Standard Features, Service and Support, Related Options, Model Selection Matrix, and Technical Specifications were updated. Note the title changed to HPE Metered Power Distribution Units (PDU). | ||||||||||||||
|
18-Aug-2014 |
From Version 8 to 9 |
Added |
Added 4.9kVA PDU and 7.3kVA PDU to Half Height vertical models in Metered PDU Family Information. | ||||||||||||||
|
Changed |
Changed "Monitoring" to "Monitored" throughout the QuickSpecs. | ||||||||||||||||
|
10-Jun-2014 |
From Version 6 to 8 |
Changed |
Changes were made throughout. | ||||||||||||||
|
25-Mar-2014 |
From Version 5 to 6 |
Changed |
Models and Standard Features were revised. | ||||||||||||||
|
07-Mar-2014 |
From Version 4 to 5 |
Changed |
Models, Standard Features, and Related Options were revised. | ||||||||||||||
|
18-Feb-2014 |
From Version 3 to 4 |
Changed |
Models, Standard Features, and Related Options were revised. | ||||||||||||||
|
15-Nov-2013 |
From Version 2 to 3 |
Changed |
Changed "Monitored" to "Monitoring" throughout the QuickSpecs. | ||||||||||||||
|
11-Oct-2013 |
From Version 1 to 2 |
Changed |
Revised the Models & Model Selection Matrix sections. | ||||||||||||||
|
| |||||||||||||||||
|
|
| |||||||||||||||
|
|
|
© Copyright 2016 Hewlett Packard Enterprise Development Company, L.P. The only warranties for Hewlett Packard Enterprise products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. Hewlett Packard Enterprise shall not be liable for technical or editorial errors or omissions contained herein. c04229509 - 14669 - Worldwide - V10 - 16-February-2016 | |||||||||||||||