Dell PowerEdge R530xd: руководство по обслуживанию

Technical specifications

Processor
Processor type One or two Intel Xeon E5 2600 V3 product family processors
Expansion Bus
Bus type PCI Express Generation 2 and PCI Express Generation 3 expansion slots with two optional riser cards.
Expansion slots (with optional expansion card risers)    
Dual riser module (uses PCIe slot 1 and PCIe slot 2 on system board) (Slot 1) One full-height, full-length x16 link (from CPU1)
    (Slot 2) One half-length, low profile x8 link (from CPU1)
  • NOTE: When a card installed in PCIe Slot2, the PCIe Slot1 will perform at PCIe x8 bandwidth only. The expansion card riser can be used with either two x8 PCIe cards or with one x16 PCIe card on PCIE slot 1.
    (Slot 3) One half-length, low profile x8 link (from CPU1)
    (Slot 4) One half-length, low profile x8 link (from CPU1)
Internal PERC riser (Slot 5) One half-length, low-profile x8 (internal, for PERC only) (from CPU2)
     
Expansion slots (without expansion card risers)   (Slot 1) One half-length, low-profile x16 (from CPU1)
    (Slot 2) One half-length, low-profile x16 (from CPU1)
    (Slot 3) One half-length, low-profile x4 (from PCH)
Memory  
Architecture 1333 MT/s, 1600 MT/s, 1866 MT/s, or 2133 MT/s DDR4 registered, Error Correcting Code (ECC) Spare Rank, Single Device Data Correction (SDDC) DIMMs
Support for advanced ECC or memory optimized operation
Memory module sockets Sixteen 288-pin sockets
Memory module capacities (RDIMM) 4 GB, 8 GB, 16 GB, and 32 GB
Minimum RAM 4 GB with a single processor
8 GB with a dual processor (minimum one memory module per processor)
Maximum RAM Up to 256 GB with a single processor
Up to 512 GB with a dual processor
Power Supply Unit Capacity
Power rating per power supply unit (hot swap) 1100 W (Platinum) AC (100-240 V, 50/60 Hz, 12 A-6.5 A)
750 W (Platinum) AC (100-240 V, 50/60 Hz, 10 A-5 A)
750 W (Platinum) DC (240 V DC, 4.5 A)
  • NOTE: For China only
495 W (Platinum) AC (100-240 V, 50/60 Hz, 6.5 A-3 A)
Heat dissipation
  • NOTE: Heat dissipation is calculated using the power supply wattage rating.
1908 BTU/hr maximum (495 W power supply)
2891 BTU/hr maximum (750 W power supply)
4100 BTU/hr maximum (1100 W power supply)
Voltage
  • NOTE: This system is also designed to be connected to IT power systems with a phase to phase voltage not exceeding 230 V.
100–240 V AC, autoranging, 50/60 Hz
Storage Controller  
Storage Controller PERC H330, PERC H730, PERC H730P, and 12Gb SAS HBA
Drives  
Hard drives Up to twelve 3.5 inch or 2.5 inch(with 3.5 inch drive carrier adapters), hot-swappable SAS, SATA, or Nearline SAS hard drives
SSD Up to twelve 3.5 inch or 2.5 inch(with hybrid drive carriers), hot-swappable SATA SSDs
Internal hard drives Up to two 2.5 inch, internal cabled SATA
  • NOTE: These internal drives are used only for the operating system. They will not be controlled by the RAID controller. These hard drives are controlled by PCH chipset.
Connectors  
Back  
  NIC Two 10/100/1000 LAN ports
  Serial 9-pin, DTE, 16550-compatible
  USB Two USB ports, 1 USB 3.0-compliant port and 1 USB2.0–compliant port
  Video 15-pin VGA
  iDRAC8 One optional vFlash memory card slot and one dedicated 1Gbe Ethernet port with iDRAC8 Enterprise card and up to two optional shared NIC ports.
  • NOTE: The card slot is available for use only if the iDRAC8 Enterprise license is installed on your system.
Front  
  USB One 4-pin, USB 2.0-compliant

One USB management port

  Video 15-pin VGA
Internal  
  SATA One Mini-SAS connectors
  USB One 9-pin, USB 3.0-compliant
  Internal Dual SD Module Two optional flash memory card slots with the internal SD module
  • NOTE: One card slot is dedicated for redundancy.
Video  
Video type Integrated Matrox G200
Video memory 16 MB shared
Physical
Height 8.68cm(3.41 inch)
Width 48.24 cm (18.99)
Depth 64.6 (25.43 inch) (with Bezel)
Maximum configuration weight 27.3Kg / 60.18lb
Empty weight 11.4Kg / 25.13lb
Environmental specifications  
  • NOTE: For additional information about environmental measurements for specific system configurations, see dell.com/environmental_datasheets.
Temperature  
  Storage –40°C to 65°C (–40°F to 149°F)
  Continuous operation (for altitude less than 950 m or 3117 ft) 10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment.
  Fresh air For information on fresh air, see Expanded Operating Temperature section.
  Maximum temperature gradient (operating and storage) 20°C/h (36°F/h)
Relative humidity  
  Storage 5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be non-condensing at all times.
  Operating 10% to 80% Relative Humidity with 29°C (84.2°F) maximum dew point.
Maximum vibration  
  Operating 0.26 G rms at 5 Hz to 350 Hz (all operation orientations).
  Storage 1.88 G rms at 10 Hz to 500 Hz for 15 min (all six sides tested).
Maximum shock  
  Operating Six consecutively executed shock pulses in the positive and negative x, y, and z axes of 40 G for up to 2.3 ms.
  Storage Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of the system) of 71 G for up to 2 ms.
Maximum altitude  
  Operating

3048 m ( 10,000 ft).

  Storage 12,000 m (39,370 ft).
Operating temperature de-rating
  Up to 35 °C (95 °F) Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m (3,117 ft).
  35 °C to 40 °C (95 °F to 104 °F) Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950 m (3,117 ft).
  40 °C to 45 °C (104 °F to 113 °F) Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950 m (3,117 ft).
Particulate contamination
  • NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for you to re-mediate the environmental conditions that are causing the damage and/or failures. Re-mediation of environmental conditions will be the responsibility of the customer.
  Air filtration
  • NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
  • NOTE: Air entering the data center must have MERV11 or MERV13 filtration.
  Conductive dust
  • NOTE: Applies to data center and non-data center environments.
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
  Corrosive dust
  • NOTE: Applies to data center and non-data center environments.
  • Air must be free of corrosive dust.
  • Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
Gaseous contamination
  • NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
  Copper coupon corrosion rate <300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
  Silver coupon corrosion rate <200 Å/month as defined by AHSRAE TC9.9.
Expanded operating temperature  
  • NOTE: When operating in the expanded temperature range, system performance may be impacted.
  • NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD and in the System Event Log.
  Continuous operation 5°C to 40°C at 5% to 85% RH with 29°C dew point.
  • NOTE: Outside the standard operating temperature (10°C to 35°C), the system can operate continuously down to 5°C or as high as 40°C.

For temperatures between 35°C and 40°C, de-rate maximum allowable temperature by 1°C per 175 m above 950 m (1°F per 319 ft).

  < 1% of annual operating hours –5°C to 45°C at 5% to 90% RH with 29°C dew point.
  • NOTE: Outside the standard operating temperature (10°C to 35°C), the system can operate down to –5°C or up to 45°C for a maximum of 1% of its annual operating hours.

For temperatures between 40°C and 45°C, de-rate maximum allowable temperature by 1°C per 125 m above 950 m (1°F per 228 ft).

  Expanded Operating Temperature Restrictions
  • Do not perform a cold startup below 5°C.
  • The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft).
  • Processors between 65 W to 120 W including 105 W (E5-2660;E5-2650), 90 W (E5-2640), 85 W (E5-2630, E5-2620, E5-2609, E5-2603) are all supported.
  • Processors below 65 W(E5-2630v3, E5-2650v3) and the 120 W processor are not supported.
  • Internal 2.5 inch hard drives are not supported.
  • Redundant power supplies are required.
  • Non Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported.