Technical specifications
| Processor | ||
|---|---|---|
| Processor type | One or two Haswell processor E5-2600 v3 product family | |
| Power | |||
|---|---|---|---|
| AC power supply (per power supply) | |||
| Wattage | 750 W, or 1100 W | ||
| Heat dissipation
NOTE: Heat dissipation is calculated using the power supply wattage rating.
|
2891 BTU/hr maximum (750 W power supply) 2843 BTU/hr maximum (750 W Titanium power supply) 4100 BTU/hr maximum (1100 W power supply) 4416 BTU/hr maximum (DC1100W power supply) 2891 BTU/hr maximum (750 W mixed mode power supply) |
||
| Voltage
NOTE: This system is also designed to be connected to IT power systems with a phase to phase voltage not exceeding 230 V.
|
100–240 V AC, autoranging, 50/60 Hz Or 200–240 V AC, autoranging, 50/60 Hz, for 750 W Titanium power supply |
||
| DC power supply (per power supply) | |||
| Wattage | 1100 W or 750 W (Platinum power supply for China only) | ||
| Heat dissipation
NOTE: Heat dissipation is calculated using the power supply wattage rating.
|
4416 BTU/hour maximum | ||
| Voltage
NOTE: This system is also designed to be connected to IT power systems with a phase to phase voltage not exceeding 230 V.
|
–(48–60) V DC | ||
| System battery | CR 2032 3.0-V lithium coin cell | ||
| Expansion Bus | |||
|---|---|---|---|
| Bus type | PCI Express Generation 3 | ||
| Expansion cards | For a list of supported expansion cards, see the Expansion cards and expansion-card risers section in this document. | ||
| Expansion slots using riser card: | |||
| Riser 1 | (Slot 1) One half-height, low-profile x8 link | ||
| (Slot 2) One half-height, low-profile x8 link | |||
| (Slot 3) One half-height, low-profile x8 link | |||
| Riser 2 | (Slot 4) One full-height, full-length x16 link | ||
|
NOTE: To use slots 1–4, both the processors must be installed.
|
|||
| (Slot 5) One full-height, full-length x8 link | |||
| Riser 3 (default) | (Slot 6) One full-height, full-length x8 link | ||
| (Slot 7) One full-height, full-length x8 link | |||
| Riser 3 (alternate for GPU) | (Slot 6) One full-height, full-length x16 link | ||
| Memory | ||
|---|---|---|
| Architecture | 1333 MT/s, 1600 MT/s, 1866 MT/s, or 2133 MT/s DDR4 registered, load-reduced Error Correcting Code (ECC) DIMMs | |
| Support for advanced ECC or memory optimized operation | ||
| Memory module sockets | Twenty-four 288-pin | |
| Memory module capacities | ||
| LRDIMMs | 32 GB quad-ranked | |
| RDIMMs | 4 GB single-ranked, 8 GB, or 16 GB dual-ranked | |
| Minimum RAM | 4 GB with a single processor | |
| 8 GB with a dual processor (minimum one memory module per processor) | ||
| Maximum RAM | Up to 768 GB with a dual processor | |
| Up to 384 GB with a single processor | ||
| Hard Drives | |
|---|---|
| Twelve plus two–hard-drive systems | Up to twelve 3.5 inch and two optional 2.5 inch back-accessible, internal, hot-swappable SAS, SATA, SAS/SATA SSD, or Nearline SAS drives in hard-drive slots 0–11 and 12–13. |
| Connectors | ||
|---|---|---|
| Back | ||
| NIC | Four 1 Gbps, two 1 Gbps plus two 10 Gbps, or four 10 Gbps | |
| Serial | 9-pin, DTE, 16550-compatible | |
| USB | Two 4-pin, USB 3.0-compliant | |
| Video | 15-pin VGA | |
| External vFlash card | One flash memory card slot with iDRAC8 Enterprise card
NOTE: The card slot is available for use only if the iDRAC8 Enterprise license is installed on your system.
|
|
| Front | ||
| USB |
One 4-pin, USB 2.0-compliant One USB management port/iDRAC Direct |
|
| Video | 15-pin VGA | |
| Internal | ||
| USB | One 4-pin, USB 3.0-compliant | |
| Internal Dual SD Module | Two optional flash memory card slots with the internal SD module
NOTE: One card slot is dedicated for redundancy.
|
|
| Video | ||
|---|---|---|
| Video type | Matrox G200eR2 | |
| Video memory | 16 MB | |
| Physical | ||
|---|---|---|
| Height | 8.73 cm (3.44 inch) | |
| Width | 48.2 cm (18.98 inch) | |
| Depth | 75.58 cm (29.75 inch) | |
| Maximum configuration weight |
|
|
| Empty weight |
|
|
| Expanded Operating Temperature | ||
|---|---|---|
|
NOTE: When operating in the expanded temperature range, system performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD and in the System Event Log.
|
||
| < 10% of annual operating hours | Continuous Operation 5 °C–40°C at 5% to 85% RH with 29°C dew point.
NOTE: Outside the standard operating temperature (10°C–35°C), the system can operate continuously down to 5°C or as high as 40°C.
For temperatures between 35°C- 40°C, derate maximum allowable temperature by 1°C per 175 m above 950 m (1°F per 319 ft). |
|
| < 1% of annual operating hours | –5 °C–45°C at 5% to 90% RH with 29°C (84.2°F) maximum dew point.
NOTE: Outside the standard operating temperature (10°C–35°C), the system can operate down to –5°C or up to 45°C for a maximum of 1% of its annual operating hours.
For temperatures between 40 °C–45 °C, derate maximum allowable dry bulb temperature by 1°C per 125 m above 950 m (1°F per 228 ft). |
|
| Expanded Operating Temperature Restrictions |
|
|
| Environmental | ||
|---|---|---|
|
NOTE: For additional information about environmental measurements for specific system configurations, see
Dell.com/environmental_datasheets.
|
||
| Temperature | ||
| Storage | –40°C–65°C (–40°F–149°F) | |
| Continuous operation (for altitude less than 950 m or 3117 ft) | 10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment. | |
|
Fresh air |
For information on fresh air, see Expanded Operating Temperature section. |
|
|
Maximum temperature gradient (operating and storage) |
20°C/h (36°F/h) |
|
| Relative humidity | ||
| Storage | 5% to 95% RH with 33°C (91 °F) maximum dew point. Atmosphere must be non-condensing always. | |
|
Operating |
10% to 80% Relative Humidity with 29°C (84.2°F) maximum dew point. |
|
| Maximum vibration | ||
| Operating | 0.26 Grms at 5 Hz to 350 Hz (all operation orientations). | |
| Storage | 1.87 Grms at 10 Hz to 500 Hz for 15 min (all six sides tested). | |
| Maximum shock | ||
| Operating | Six consecutively executed shock pulses in the positive and negative x, y, and z axes of 40 G for up to 2.3 ms. | |
| Storage | Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of the system) of 71 G for up to 2 ms. | |
| Maximum altitude | ||
| Operating |
3,048 (10,000 ft) |
|
| Storage | 12,000 m (39,370 ft). | |
| Operating altitude de-rating | ||
| Up to 35°C (95°F) | Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m (3,117 ft). | |
| 35 °C–40°C (95 °F–104°F) | Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950 m (3,117 ft). | |
| 40 °C–45°C (104 °F–113°F) | Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950 m (3,117 ft). | |
| Particulate contamination
NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for you to re-mediate the environmental conditions that are causing the damage and/or failures. Re-mediation of environmental conditions will be the responsibility of the customer.
|
||
| Air filtration
NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.
|
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95 percent upper confidence limit.
NOTE: Air entering the data center must have MERV11 or MERV13 filtration.
|
|
| Conductive dust
NOTE: Applies to data center and non-data center environments.
|
Air must be free from conductive dust, zinc whiskers, or other conductive particles. | |
| Corrosive dust
NOTE: Applies to data center and non-data center environments.
|
|
|
| Gaseous contamination | ||
|
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
|
||
| Copper coupon corrosion rate | <300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985. | |
| Silver coupon corrosion rate | <200 Å/month as defined by AHSRAE TC9.9. | |