Chassis dimensions
| System | Dimension in mm | ||
|---|---|---|---|
| X | Y | Z | |
| M830 | 395.20 | 50.35 | 545.0 |
Chassis weight
Maximum chassis weight of the PowerEdge M830 system is 14.5 kg (31.9 lb).
Processor specification
System battery specification
Memory specifications
| Memory module socket | Memory capacity | Minimum RAM | Maximum RAM |
|---|---|---|---|
| Forty-eight 240-pin |
|
4 GB with dual processor | 3 TB with four processor |
RAID controller specifications
Hard drives
- Up to four 2.5-inch SAS/SATA/PCIe SSDs or SAS/SATA hard drives
- Up to twelve 1.8-inch SAS SSDs
Optical drives
Flash drive
- Internal optional USB
- Internal optional SD card
- Optional vFlash card (with integrated iDRAC Enterprise)
USB ports
- One 4-pin, USB 2.0-compliant and one 9-pin, USB 3.0-compliant on the front panel
- Internal two 4-pin, USB 2.0-compliant
SD cards
Mezzanine card specification
The PowerEdge M830 system supports four PCIe x8 Gen 3 slots mezzanine card supporting dual-port 10 Gb Ethernet, quad port 1 Gb, FC8 Fiber Channel, FC16 Fiber Channel, or Infiniband mezzanine cards.
Video specifications
Environmental specifications
| Temperature | Specifications |
|---|---|
| Storage | –40°C to 65°C (–40°F to 149°F) |
| Continuous operation (for altitude less than 950 m or 3117 ft) | 10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment |
| Fresh air | For information about fresh air, see the Expanded Operating Temperature section. |
| Maximum temperature gradient (operating and storage) | 20°C/h (36°F/h) |
| Relative humidity | Specifications |
|---|---|
| Storage | 5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be non-condensing at all times. |
| Operating | 10% to 80% RH with 29°C (84.2°F) maximum dew point. |
| Maximum vibration | Specifications |
|---|---|
| Operating | 0.26 Grms at 5 Hz to 350 Hz (all operation orientations) |
| Storage | 1.88 Grms at 10 Hz to 500 Hz for 15 minutes (all six sides tested) |
| Maximum shock pulse | Specifications |
|---|---|
| Operating | Six consecutively executed shock pulses in the positive and negative x, y, and z axes of 40 G for up to 2.3 ms. |
| Storage | Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of the system) of 71 G for up to 2 ms. |
| Maximum altitude | Specifications |
|---|---|
| Operating | 3048 m (10,000 ft) |
| Storage | 12,000 m (39,370 ft) |
| Operating temperature de-rating | Specifications |
|---|---|
| Up to 35°C (95°F) | Maximum temperature is reduced by 1°C/300 m (1°F/547 ft), above 950 m (3,117 ft). |
| 35 °C to 40 °C (95 °F to 104 °F) | Maximum temperature is reduced by 1°C/175 m (1°F/319 ft), above 950 m (3,117 ft). |
| 40 °C to 45 °C (104 °F to 113 °F) | Maximum temperature is reduced by 1°C/125 m (1°F/228 ft), above 950 m (3,117 ft). |
Particulate and gaseous contamination specifications
| Particulate contamination | Specifications |
|---|---|
| Air Filtration | Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit. NOTE: This condition
applies to data center environments only. Air filtration requirements
do not apply to IT equipment designed to be used outside a data center,
in environments such as an office or factory floor. NOTE: Air entering the data
center must have MERV11 or MERV13 filtration. |
Conductive dust |
Air must be free of conductive dust, zinc whiskers, or other conductive particles. NOTE: This condition applies
to data center and nondata center environments. |
Corrosive dust |
NOTE: This condition
applies to data center and nondata center environments. |
| Gaseous contamination | Specifications |
|---|---|
| Copper Coupon Corrosion | <300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985. |
| Silver Coupon Corrosion | <200 Å/month as defined by AHSRAE TC9.9. |
Expanded operating temperature
| Expanded operating temperature | Specifications |
|---|---|
| Continuous operation | 5°C to 40°C at 5% to 85% RH with 29°C dew point. NOTE: Outside the standard
operating temperature (10°C to 35°C), the system can operate continuously
in temperatures as low as 5°C and as high as 40°C. For temperatures between 35°C and 40°C, de-rate maximum allowable temperature by 1°C per 175 m (1°F per 319 ft.) above 950 m (3,1171 ft.). |
| ≤ 1% of annual operating hours | –5°C to 45°C at 5% to 90% RH with 29°C dew point. NOTE: Outside the standard
operating temperature (10°C to 35°C), the system can operate down
to –5°C or up to 45°C for a maximum of 1% of its annual operating
hours. For temperatures between 40°C and 45°C, de-rate maximum allowable temperature by 1°C per 125 m (1°F per 228 ft.) above 950 m (3.117 ft.). |
Expanded operating temperature restrictions
- Do not perform a cold startup below 5 °C
- Install only 94 mm wide heat sinks
- Do not install more than 40 DIMMs
- The following do not support expanded operating temperature range:
- PCIe SSD
- Express flash
- LRDIMMs
- 130 W or 120 W all core processors
- Non Dell-qualified peripheral cards and/or peripheral cards greater than 25 W