Dell PowerEdge FX2 and FX2s Enclosure: руководство по обслуживанию

Dimensions and weight

Physical
Dimensions
Width
With rack ears
481.9 mm (18.97 in)
Without rack ears
43.35 cm (17.06 inch)
Height
86.80 mm (3.4 in)
Depth (without bezel)
851.6 mm (33.52 in)
Maximum configuration weight
53 kg (116.8 lb)
Empty weight
21.5 kg (47.4 lb)

Sled specifications

Compute sleds
Specifications
PowerEdge FX2
Up to four half-width PowerEdge FC630/FC640 or PowerEdge FM120x4 compute sleds, or

Up to eight PowerEdge FC430 compute sleds, or

Up to two PowerEdge FC830 compute sleds, or

Up to four PowerEdge FC430 compute sleds mixed with up to two PowerEdge FC630/FC640 compute sleds, or

One PowerEdge FC830 compute sled mixed with up to two PowerEdge FC630/FC640 compute sleds

PowerEdge FX2s
Up to four half-width PowerEdge FC630/FC640 compute sleds, or

Up to eight PowerEdge FC430 compute sleds, or

Up to two PowerEdge FC830 compute sleds, or

Up to four PowerEdge FC430 compute sleds mixed with up to two PowerEdge FC630/FC640 compute sleds, or

One PowerEdge FC830 compute sled mixed with up to two PowerEdge FC630/FC640 compute sleds

Storage sleds
Specifications
PowerEdge FX2s

Up to three PowerEdge FD332 storage sleds mapped to one PowerEdge FC630/FC640 compute sled, or

Up to two PowerEdge FD332 storage sleds mapped to two PowerEdge FC630/FC640 compute sleds, or

Up to two PowerEdge FD332 storage sleds mapped to up to four PowerEdge FC430 compute sleds, or

Up to two PowerEdge FD332 storage sleds mapped to one PowerEdge FC830 compute sled

NOTE: For more information on the technical specifications for the compute and storage sled(s), see the relevant sled Owner's Manual at Dell.com/poweredgemanuals.
NOTE: For information on mapping of storage sleds to compute sleds in the PowerEdge FX2s enclosure, see the Dell PowerEdge FD332 Owner's Manual at Dell.com/poweredgemanuals.

Power specifications

Power supply unit
Specifications
Wattage
1100 W (1050 W for low line)

1600 W (800 W for low line)

2000 W (1000 W for low line)

2400 W (1400 W for low line)

Connector
Card Edge
Heat dissipation
394 BTU/hr (full load for the power supply unit only) (1100 W power supply unit)
475 BTU/hr (full load for the power supply unit only) (1600 W power supply unit)
635 BTU/hr (full load for the power supply unit only) (2000 W power supply unit)
760 BTU/hr (full load for the power supply unit only) (2400 W power supply unit)
Maximum inrush current
25 A
System voltage requirements
100 – 240 V AC
NOTE: This system is also designed to be connected to IT power systems with a phase to phase voltage not exceeding 230 V.

Chassis Management Controller (CMC) specifications

Externally accessible connectors
Specifications
Remote management
Two dedicated 10/100/1000 Mb RJ-45 (for integrated Ethernet remote access controller). Gb port connects to the CMC module’s external management network. STK port allows CMCs in adjacent enclosures to be daisy chained. The STK port can also be used for CMC NIC failover.
Serial
9-pin, DTE, 16550-compatible

Enclosure control panel specifications

Externally accessible connectors
Specifications
USB
One 4-pin, USB 1.1-compliant connector for keyboard and mouse support.
Video
15-pin VGA

I/O module specifications

NOTE: For information on the technical specifications for the I/O modules, see the I/O module documentation at Dell.com/poweredgemanuals.

Environmental specifications

NOTE: For additional information about environmental measurements for specific system configurations, see Dell.com/environmental_datasheets.
Temperature
Specifications
Maximum Temperature Gradient (Operating and Storage)
20 °C/h (36 °F/h)
Storage Temperature Limits
–40 °C to 65 °C (–40 °F to 149 °F)
Relative humidity
Specifications
Storage
5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be non-condensing at all times.
Temperature (Continuous Operation)
Specifications
Temperature Ranges (for altitude less than 950 m or 3117 ft)
10 °C to 35 °C (50 °F to 95 °F) with no direct sunlight on the equipment.
Humidity Percentage Range
10% to 80% Relative Humidity with 26 °C (78.8 °F) maximum dew point.
Maximum vibration
Specifications
Operating
0.26 Grms at 5 Hz to 350 Hz (all operation orientations).
Storage
1.87 Grms at 10 Hz to 500 Hz for 15 min (all six sides tested).
Maximum shock
Specifications
Operating
One shock pulse in the positive z axis of 31 G for 2.6 ms in all operational orientations.
Storage
Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of the system) of 71 G for up to 2 ms.
Maximum altitude
Specifications
Operating
3,048 m (10,000 ft)
Storage
12,000 m (39,370 ft).
Operating temperature de-rating
Specifications
Up to 35 °C (95 °F)
Maximum temperature is reduced by 1 °C/300 m (1 °F/547 ft) above 950 m (3,117 ft).
35 °C to 40 °C (95 °F to 104 °F)
Maximum temperature is reduced by 1 °C/175 m (1 °F/319 ft) above 950 m (3,117 ft).
40 °C to 45 °C (104 °F to 113 °F)
Maximum temperature is reduced by 1 °C/125 m (1 °F/228 ft) above 950 m (3,117 ft).

The following section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If the levels of particulates or gaseous pollution are beyond the specified limits and cause equipment damage or failure, you may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.

Particulate contamination
Specifications
Air filtration
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.
NOTE: Air entering the data center must have MERV11 or MERV13 filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
NOTE: Applies to data center and non-data center environments.
Corrosive dust
  • Air must be free of corrosive dust.
  • Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE: Applies to data center and non-data center environments.
Gaseous contamination
Specifications
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
Silver coupon corrosion rate
<200 Å/month as defined by AHSRAE TC9.9.
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.

Expanded operating temperature

Expanded operating temperature
Specifications
< 10% of annual operating hours
5°C to 40°C at 5% to 85% RH with 26 °C dew point.
NOTE: Outside the standard operating temperature (10°C to 35°C), the system can operate down to 5°C or up to 40°C for a maximum of 10% of its annual operating hours.

For temperatures between 35°C and 40°C, de-rate maximum allowable dry bulb temperature by 1°C per 175 m above 950 m (1°F per 319 ft).

< 1% of annual operating hours
9–5°C to 45°C at 5% to 90% RH with 26°C dew point.
NOTE: Outside the standard operating temperature (10°C to 35°C), the system can operate down to –5°C or up to 45°C for a maximum of 1% of its annual operating hours.

For temperatures between 40°C and 45°C, de-rate maximum allowable dry bulb temperature by 1°C per 125 m above 950 m (1°F per 228 ft).

Expanded operating temperature restrictions
  • Do not perform a cold startup below 5°C.
  • The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft).
  • Two redundant power supplies are required.
  • Non Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported.
NOTE: For more information on the sled-specific restrictions for the expanded operating temperature range, see the technical specifications in the sled Owner's Manual at Dell.com/poweredgemanuals.