Chassis dimensions and weight

| System | X | Y | Z |
|---|---|---|---|
| FC430 | 102.7 mm | 40.3 mm | 480.36 mm |
| System | Chassis weight |
|---|---|
| FC430 | 3.0 kg (6.61 lb) |
Processor specifications
The PowerEdge
FC430 system supports up to two Intel Xeon E5-2600 v4 processors.
System battery specification
The PowerEdge
FC430 system supports CR 2032 3.0-V lithium coin cell system battery.
Memory specifications
The PowerEdge FC430 system supports DDR4 registered DIMMs (RDIMMs and LRDIMMs).
Memory module sockets |
Memory capacity |
Minimum RAM |
Maximum RAM |
|---|---|---|---|
| Eight 288-pin | 4 GB, 8 GB, 16 GB, and 32 GB (RDIMMs) | 4 GB (RDIMM) | 256 GB (RDIMM) |
| 64 GB (LRDIMM) | 64 GB (LRDIMM) | 512 GB (LRDIMM) |
RAID controller
The PowerEdge
FC430 system supports PERC S130 controller.
SSD specification
The PowerEdge
FC430 system supports up to two 1.8-inch uSATA SSDs.
USB ports
The PowerEdge
FC430 system supports:
- One 4-pin, USB 3.0 compliant port
- USB management port or iDRAC Direct port which supports USB 2.0 compliant port
QSFP+ port
The QSFP+
port is used for Infiniband or Ethernet.
PCIe Mezzanine card
The PowerEdge
FC430 system supports one PCIe x8 mezzanine slot supporting a single
or dual port InfiniBand mezzanine card.
Video specification
The PowerEdge
FC430 supports Matrox G200eR2 video controller. The available memory is 16 MB which is shared with the iDRAC application memory.
Environmental specifications
NOTE:For additional information
about environmental measurements for specific system configurations,
see Dell.com/environmental_datasheets.
| Temperature | Specifications |
|---|---|
| Storage | –40°C to 65°C (–40°F to 149°F) |
| Continuous operation (for altitude less than 950 m or 3117 ft) | 10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment |
| Maximum temperature gradient (operating and storage) | 20°C/h (36°F/h) |
| Relative humidity | Specifications |
|---|---|
| Storage | 5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be non-condensing at all times. |
| Operating | 10% to 80% RH with 29°C (84.2°F) maximum dew point. |
| Maximum vibration | Specifications |
|---|---|
| Operating | 0.26 Grms at 5 Hz to 350 Hz (all operation orientations) |
| Storage | 1.87 Grms at 10 Hz to 500 Hz for 15 minutes (all six sides tested) |
| Maximum shock pulse | Specifications |
|---|---|
| Operating | One shock pulse in the positive z axes of 31 G for 2.6 ms in all operational orientations. |
| Storage | Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of the system) of 71 G for up to 2 ms. |
| Maximum altitude | Specifications |
|---|---|
| Operating | 3048 m (10,000 ft) |
| Storage | 12,000 m (39,370 ft) |
| Operating temperature de-rating | Specifications |
|---|---|
| Up to 35°C (95°F) | Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m (3,117 ft) |
Particulate and gaseous contamination specifications
The following
table defines the limitations that will help avoid any damages to
the IT equipment and/or failure from particulates and gaseous contamination.
If the levels of particulates or gaseous pollution exceed the specified
limitations and result in equipment damage or failure, you may need
to rectify the environmental conditions. Re-mediation of environmental
conditions is the responsibility of the customer.
| Particulate contamination | Specifications |
|---|---|
| Air Filtration | Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit. NOTE:This condition
applies to data center environments only. Air filtration requirements
do not apply to IT equipment designed to be used outside a data center,
in environments such as an office or factory floor. NOTE:Air entering the data
center must have MERV11 or MERV13 filtration. |
Conductive dust |
Air must be free of conductive dust, zinc whiskers, or other conductive particles. NOTE:This condition applies
to data center and nondata center environments. |
Corrosive dust |
NOTE:This condition
applies to data center and nondata center environments. |
| Gaseous contamination | Specifications |
|---|---|
| Copper Coupon Corrosion | <300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985. |
| Silver Coupon Corrosion | <200 Å/month as defined by AHSRAE TC9.9. |
NOTE:Maximum
corrosive contaminant levels measured at ≤50% relative humidity.
Standard operating temperature
| Standard operating temperature | Specifications |
|---|---|
| Continuous Operation (for altitude less than 950 m or 3117 ft) | 10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment. |
Expanded operating temperature restrictions
| System | Processor configuration (in watts) | DIMM | Operating temperature |
|---|---|---|---|
| Dual processor system | 120 W | RDIMM: 4 GB, 8 GB, 16 GB, and 32 GB |
Up to 25ºC ambient |
| 120 W | LRDIMM: 64 GB | Up to 20ºC ambient | |
| 105 W | RDIMM: 4 GB, 8 GB, 16 GB, and 32 GB |
Up to 30ºC ambient | |
| 105 W | LRDIMM: 64 GB | Up to 25ºC ambient | |
| 90 W | RDIMM: 4 GB, 8 GB, 16 GB, and 32 GB LRDIMM: 64 GB |
Up to 30ºC ambient | |
| <=85 W | RDIMM: 4 GB, 8 GB, 16 GB, and 32 GB | Up to 35ºC ambient | |
| <=85 W | LRDIMM: 64 GB | Up to 30ºC ambient | |
| Single processor system | 140 W | RDIMM: 4 GB, 8 GB, 16 GB, and 32 GB LRDIMM: 64 GB |
Up to 30ºC ambient |
| 135 W | RDIMM: 4 GB, 8 GB, 16 GB, and 32 GB LRDIMM: 64 GB |
Up to 30ºC ambient | |
| <=120 W | RDIMM: 4 GB, 8 GB, 16 GB, and 32 GB LRDIMM: 64 GB |
Up to 35ºC ambient |