Technical specifications
This section describes the technical specifications of the MD2412 and the MD2424 enclosures.
Enclosure dimensions
| Specification | MD2412 | MD2424 |
|---|---|---|
| Height | 2U
86.8 mm (3.4 in.) |
2U
86.8 mm (3.4 in.) |
| Width | 444 mm (17.5 in.) | 444 mm (17.5 in.) |
| Depth | 545 mm (21.5 in.) | 497 mm (19.5 in.) |
Enclosure weights
| Component | MD2412 | MD2424 |
|---|---|---|
| Storage enclosure (empty) | 9.5 kg (21 lb) | 9.2 kg (20.25 lb) |
| Drive with carrier (each) | 0.8 kg (1.76 lbs) | 0.24 kg (0.53 lbs) |
| EMM (each) | 2.43 kg ( 5.36 lb) | 2.52 kg ( 5.55 lb) |
| PSU (each) | 0.81 kg (1.79 lb) | 0.89 kg (1.96 lb) |
| System without drives | 15.98 kg (35.23 lb) | 16.0 kg (35.27 lb) |
| System with all drives installed | 25.58 kg (56.39 lb) | 21.76 kg (47.99 lb) |
- Weights that are shown are nominal, and subject to variances.
- Weights may vary due to different canisters and power supplies; and differing calibrations between scales.
- Weights may also vary due to the number and type of disk drives (SAS or SSD) installed.
Environmental requirements
| Specification | Temperature range | Relative humidity | Max. Temperature Gradient |
|---|---|---|---|
| Operating | 0°C to 40°C (32°F to 104°F) | 8% to 85% non-condensing | 20°C per hour |
| Operating (ASHRAE A3) | 5°C to 40°C (41°F to 104°F) | 8% to 85% non-condensing | 20°C per hour |
| Non-operating | -40°C to +65°C (-40°F to +149°F) | 10% to 95% non-condensing | - |
| Specification | Temperature range | Relative humidity | Max. Temperature Gradient |
|---|---|---|---|
| Operating - altitude less than or equal to 1829 meters (6000 ft) | 5°C to 40°C (41°F to 104°F) | 5% to 85% non-condensing | 30°C per hour |
| Short term 2 | -5°C to 50°C (23°F to 122°F) | 5% to 93% not to exceed 0.026 kg water/kg of dry air | - |
| Short term with fan failure | -5°C to 40°C (23°F to 104°F) | - | - |
1 This table is a high-level summary of NEBS requiremetns. For a complete list of requirements see NEBS GR-63-CORE. All other requirements found in GR-63-CORE also apply.
2Short-term refers to a period of not more than 96 consecutive hours and a total of not more than 15 days in 1 year. (This refers to a total of 360 hours in any given year, but not more than 15 occurrences during that 1-year period.)
| Specification | Measurement or description |
|---|---|
| Altitude, operating | 900 meters @ 45°C ; 3050 meters @ 33°C
NOTE:Ramp Altitude at 3.81m/s and temperature at 20˚C/Hr
|
| Altitude, non-operating | Maximum 12,000 m (39,370 ft) |
| Shock, operating | 6.0 g, 11 ms. Four shocks positive and four negative in each of 3 axes, 24 total shocks. |
| Shock, non-operating square shock | 25g, 3ms. Three shocks positive and three negative in each of 3 axes, 18 total shocks. |
| Shock, non-operating half sine shock | 50g, 2ms. One time per face (except front and rear face), total 4 shocks. |
| Vibration, operating | 0.21 Grms 5 Hz–500 Hz random; 10 minutes/axis |
| Vibration, non-operating, random chassis | 0.47 Grms; 4–5 00Hz; vertical axis; random; 90 minutes per axis
0.39 Grms; 4–500Hz; horizontal axis; random; 30 minutes per axis |
| Vibration, non-operating, random rack | 0.88 Grms; 2–200Hz; random; minutes in normal shipping orientation |
| Vibration, transporting | 1.15Grms 1 ~–200 Hz; 4 sides (bottom, top, left, right). 30 minutes per side based on ISTA 2A Standard |
| Acoustics | Operating sound power ≤ 8.0 Bels LWAd (@ 23 ± 2°C ) |
Power-on and reset
The firmware boot time from power-on reset or soft reset to SMP target readiness is typically less than two minutes. Actual boot time may vary depending on your specific configuration.
Power supply unit
| Specification | Measurement |
|---|---|
| Maximum output power | 800 W |
| Voltage |
|
| Frequency | 50/60 Hz |
| Holdup time | 10 ms |
| Inrush current | 55 A (maximum) |
| Leakage current | 0.875 mA (maximum) |
| Efficiency | 230 VRMS
|
| Power factor | 115 Vac 50Hz/240 Vac 60 Hz
|
| iTHD | Maximum iTHD%
|
| Specification | Measurement |
|---|---|
| Voltage | –40 VDC to –72 VDC (-48 VDC nominal) |
| Leakage current | 3.5 mA (maximum) |
- The MD24 Series enclosure using a DC power supply is suitable for installation as part of the common bonding network (CBN) of an isolated bonding network (IBN) or both.
- The battery return (BR) input for each DC-powered product is isolated from the MD24 Series enclosure common DC return.