Technical Specifications
| Physical disks | Up to twelve 3.5 inch or twenty-four 2.5 inch SAS, nearline SAS physical disks, or SAS SSDs | |
| RAID controller modules | Two hot-swappable modules
with temperature sensors 4GB or 8GB of cache per controller |
|
| Provides host-to-controller 16G FC connection | ||
| Dell PowerVault MD1200 and MD1220 expansion enclosures | Each expansion enclosure
holds Up to twelve 3.5 inch or twenty-four 2.5 inch SAS, nearline
SAS physical disks, or SAS SSDs Redundant path connectivity provides redundant data paths to each hard drive NOTE: Support for 192 physical
disks is a premium feature and requires activation. |
||
| SAS connectors | Two SAS IN ports to connect
hosts One SAS OUT port for expansion to additional PowerVault MD1200 or MD1220 expansion enclosure NOTE: SAS connectors are
SFF-8088 compliant. |
||
| Serial connector (debug port) | One 6-pin mini-DIN connector NOTE: For technical support
use only. |
||
| SAS connectors | Two SAS OUT ports for
expansion to an additional PowerVault MD1200 or MD1220 expansion enclosures NOTE: SAS connectors
are SFF-8088 compliant. NOTE: It is recommended that
you use one port. |
|
| FC connectors | Four FC IN ports to connect hosts | |
| Serial connector (debug port) | One mini-USB port NOTE: For technical support
use only. |
|
| Management Ethernet connector | One 100/1000 Mbps Ethernet connection for out-of-band management of the enclosure (MGMT) |
| AC power supply (per power supply) | ||
| Wattage | 600 W | |
| Heat dissipation (maximum) NOTE: Heat dissipation is
calculated using the power supply wattage rating. The heat dissipation
values are for the entire system which includes chassis and two controllers. |
100 W | |
| Voltage NOTE: This system is also
designed to be connected to IT power systems with a phase to phase
voltage not exceeding 230 V. |
100–220 V AC, (8.6 A-4.3 A) | |
| Battery | 6.6 V DC, 1100 mAh, 7.26 W Lithium ion battery | |
NOTE: For additional
information about environmental measurements for specific system configurations,
see dell.com/environmental_datasheets. |
||
| Temperature | ||
| Operating | Continuous operation: 10
°C to 35 °C (50 °F to 95 °F) at 20% to 80% relative humidity (RH),
with 26 °C maximum dew point. De-rate maximum allowable dry bulb temperature
at 1 °C/300 m (1 °F per 550 ft) above 900 m (2952.75 ft). NOTE: For information on
supported expanded operating temperature range and configurations,
see the Owner's Manual at dell.com/powervaultmanuals. |
|
| Storage | –40 °C to 65 °C (–40 °F to 149 °F) with a maximum temperature gradation of 20 °C per hour | |
| Relative humidity | ||
| Operating | 10% to 80% (noncondensing) with maximum humidity gradation of 10% per hour | |
| Storage | 5% to 95% at a maximum wet bulb temperature of 33 °C (91 °F) | |
| Maximum vibration | ||
| Operating | 0.26 Grms at 5 Hz to 350 Hz in operational orientation | |
| Storage | 1.88 Grms at 10 Hz to 500 Hz for 15 minutes (all six sides tested) | |
| Maximum shock | ||
| Operating | One shock pulse in the positive z axis of the system at 31 G for 2.6 ms in the operational orientation |
|
| Storage | Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of the system) at 71 G for up to 2 ms | |
| Altitude | ||
| Operating | Maximum 3000 m (9842.5 ft) NOTE: For altitudes above
2950 ft, the maximum operating temperature is derated 1.8 ºF/1000
ft. |
|
| Storage | Maximum 12192 m ( 40,000 ft) | |
| Airborne contaminant level | ||
| Class | G1 as defined by ISA-S71.04-1985 | |
NOTE: This section defines
the limits to help avoid IT equipment damage and/or failure from particulates
and gaseous contamination. If it is determined that levels of particulates
or gaseous pollution are beyond the limits specified below and are
the reason for the damage and/or failures to your equipment, it may
be necessary for you to re-mediate the environmental conditions that
are causing the damage and/or failures. Re-mediation of environmental
conditions will be the responsibility of the customer. |
||
| Air Filtration NOTE: Applies to data center
environments only. Air filtration requirements do not apply to IT
equipment designed to be used outside a data center, in environments
such as an office or factory floor. |
Data center air filtration as defined
by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit. NOTE: Air entering the data
center must have MERV11 or MERV13 filtration. |
|
| Conductive Dust NOTE: Applies to data center
and non-data center environments. |
Air must be free of conductive dust, zinc whiskers, or other conductive particles. | |
| Corrosive Dust NOTE: Applies to data center
and non-data center environments. |
|
|
| Gaseous Contamination | ||
NOTE: Maximum corrosive contaminant
levels measured at ≤50% relative humidity. |
||
| Copper Coupon Corrosion Rate | <300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985. | |
| Silver Coupon Corrosion Rate | <200 Å/month as defined by AHSRAE TC9.9. | |