Technical Specifications
| Physical | |
|---|---|
| Height | 44.0 cm (17.3 inch) |
| Width | 44.7 cm (17.6 inch) |
| Depth | 75.5 cm (29.7 inch) |
| Weight (maximum) | 200.5 kg (442 lb) |
| Weight (empty) | 44.6 kg (98.1 lb) |
| Power Supply Module | |
|---|---|
| AC/DC power supply (per power supply module) (2700 W) | |
| Wattage | 2700 W |
| Connector | IEC C20 |
| Heat dissipation | 1205 BTU/hr (maximum) |
| Maximum inrush current | Under typical line conditions and over the entire system ambient operating range, the inrush current may reach 55 A per power supply for 10 ms or less. |
| AC/DC power supply (per power supply module) (3000 W) | |
| Wattage | 3000 W |
| Connector | IEC 320 |
| Heat dissipation
NOTE: Heat dissipation is calculated using the power supply wattage rating.
|
1200 BTU/hr (maximum) |
| Maximum inrush current | Under typical line conditions and over the entire system ambient operating range, the inrush current may reach 55 A per power supply for 10 ms or less. |
| System voltage requirements | 16 A, 200 V AC to 240 V AC, 50 Hz/60 Hz (3000 W power supply) |
|
NOTE: This system is also designed to be connected to IT power systems with a phase to phase voltage not exceeding 230 V.
|
16 A, 100 V AC to 240 V AC, 50 Hz/60 Hz (2700 W power supply) |
| DC/DC power supply (per power supply) | |
| Wattage | 2700 W |
| Connector | Molex # 394260002 at PSU end, mating connector Molex # 39422-0012 |
| Heat dissipation | 1205 BTU/hr (maximum) |
| Maximum inrush current | Under typical input voltage conditions and over the entire system ambient operating range, the inrush current may reach 120 A per power supply for 10 ms or less. |
| System voltage requirements | 75 A, 48 V DC to 60 V DC |
| Optional Avocent iKVM Module | |
|---|---|
| Externally accessible connectors | |
| USB | Two 4-pin, USB 2.0-compliant connectors for keyboard and mouse support |
| ACI port | RJ-45 |
| Video | 15-pin VGA |
| Chassis Management Controller Module | |
|---|---|
| Externally accessible connectors | |
| Remote management | Two dedicated 10/100/1000 Mb RJ-45 (for integrated Ethernet remote access controller). Gb port connects to the external management network. STK port allows CMCs in adjacent enclosures to be daisy chained. |
| Serial | 9-pin, DTE, 16550-compatible |
| Video | 15-pin VGA |
| Battery | CR 2032 3.0-V Lithium ion coin cell |
| Enclosure Control Panel | |
|---|---|
| Externally accessible connectors | |
| USB | Two 4-pin, USB 2.0-compliant connectors for keyboard and mouse support |
| Video | 15-pin VGA |
| LCD panel features | Four cursor control keys, one select key, LCD screen |
| Cisco Nexus B22 Fabric Extender Module | |
|---|---|
| Externally accessible connectors | Sixteen 10 Gb (internal) Ethernet ports and Eight 10 Gigabit Ethernet SFP+ ports that support 10Gbase-SR, 10Gbase-LR, and 10Gbase-ER fabric connections. |
| Brocade M6505 16 Gbps FC SAN I/O Module | |
| Externally accessible connectors | Eight physical FC8 ports that support 4/8/16 Gbps fibre channel connections |
| Serial Port | RJ-45 |
| Dell PowerEdge M I/O Aggregator Switch Module | |
| Externally accessible connectors | |
| Serial | 4-pin, USB 2.0 type A connector. Must use provided USB type A to DB9 adapter to connect to terminal. |
| Optional Modules | Two fixed 40 GbE ports that operate in 4x10 GbE mode. |
| Dell Force10 MXL 10/40 GbE Switch Module | |
| Externally accessible connectors | |
| Serial | 4-pin, USB 2.0 type A connector. Must use provided USB type A to DB9 adapter to connect to terminal. |
| Optional Modules | Two optional bays. Each bay supports an Uplink module with four 40 GbE optical SFP+ connectors, or 10GBASE-T module using RJ-45 connectors. |
| PowerConnect M8024 10 Gb Ethernet Switch Module | |
| Externally accessible connectors | |
| Serial | 4-pin, USB 2.0 type A connector. Must use provided USB type A to DB9 adapter to connect to terminal. |
| Optional Modules | Two optional bays. Each bay supports an Uplink module with four 10 Gb optical SFP+ connectors, or three 10 Gb CX4 uplinks. A stacking module is not available. |
| PowerConnect M6220 Ethernet Switch Module | |
| Externally accessible connectors | |
| 10/100/1000 Mbps Ethernet | Four autonegotiating RJ-45 ports |
| Serial | 4-pin, USB 2.0 type A connector. Must use provided USB type A to DB9 adapter to connect to terminal. |
| Optional Modules | Two option bays. Each bay supports a module with two 24 Gb stacking ports, two 10 Gb CX4 copper uplinks, or two 10 Gb optical XFPs. |
| Brocade FC8 Fibre Channel Switch Module | |
| Externally accessible connectors | Eight physical FC8 ports (four enabled by default, upgradeable to eight) that support 2/4/8 Gbps fibre channel connections |
| Serial Port | RJ-45 |
| Brocade FC4 Fibre Channel Switch Module | |
| Externally accessible connectors | |
| Fibre channel | Eight physical FC4 ports (four enabled by default, upgradeable to eight) that support 1/2/4 Gbps FC connections |
| Serial Port | RJ-45 |
| Mellanox M4001F/M4001Q Infiniband Switch I/O Module | |
| Externally accessible connectors | |
| Infiniband ports | Sixteen QSFP connectors |
| Mellanox Infiniband Switch Module | |
| Externally accessible connectors | |
| Infiniband ports | Eight Infiniband uplink ports |
| Mellanox Infiniband Switch Module | |
| Externally accessible connectors | |
| Infiniband ports | Eight Infiniband uplink ports |
| Gb Ethernet Pass-Through Module | |
| Externally accessible connectors | |
| Ethernet | Sixteen RJ-45 ports. Pass-through ports support 10/100/1000 Mbps connections. |
| Fibre Channel Pass-Through Module | |
| Externally accessible connectors | |
| Fibre channel transceiver | Sixteen external SFP ports that support 1/2/4 Gbps FC connections |
| Environmental | ||
|---|---|---|
|
NOTE: For additional information about environmental measurements for specific system configurations, see
dell.com/environmental_datasheets.
|
||
| Standard Operating Temperature | Continuous operation: 10 °C to 35 °C at 10% to 80% relative humidity (RH), with 26 °C max dew point. De-rate maximum allowable dry bulb temperature at 1 °C per 300 m above 900 m (1 °F per 550 ft). | |
| Expanded Operating Temperature | ||
|
NOTE: When operating in the expanded temperature range, system performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD and in the System Event Log.
|
||
| < 10% of annual operating hours | 5 °C to 40 °C at 5% to 85% RH with 26 °C dew point.
NOTE: Outside the standard operating temperature (10 °C to 35 °C), the system can operate down to 5 °C or up to 40 °C for a maximum of 10% of its annual operating hours.
For temperatures between 35 °C and 40 °C, de-rate maximum allowable dry bulb temperature by 1 °C per 175 m above 950 m (1 °F per 319 ft). |
|
| < 1% of annual operating hours | –5 °C to 45 °C at 5% to 90% RH with 26 °C dew point.
NOTE: Outside the standard operating temperature (10 °C to 35 °C), the system can operate down to –5 °C or up to 45 °C for a maximum of 1% of its annual operating hours.
For temperatures between 40 °C and 45 °C, de-rate maximum allowable dry bulb temperature by 1 °C per 125 m above 950 m (1 °F per 228 ft). |
|
| Expanded Operating Temperature Restrictions |
|
|
| Storage Temperature | –40 °C to 65 °C (–40 °F to 149 °F) with a maximum temperature gradation of 20 °C per hour. | |