Chassis dimensions

| Xa | Xb | Y | Za | Zb | Zc |
|---|---|---|---|---|---|
| 482.4 mm | 434 mm | 43.1 mm | 18.0 mm | 885.8 mm | 924.8 mm |
Chassis weight
| System | Maximum weight |
|---|---|
| PowerEdge C4130 (with PCIe GPUs) | 22.13 kg (48.79 lb) |
| PowerEdge C4130 (with SXM2 GPUs) | 22.73 kg (50.11 lb) |
Processor specifications
PSU specifications
| PSU | Class | Heat dissipation (maximum) | Frequency | Voltage |
|---|---|---|---|---|
| 1100 W AC | Platinum | 4100 BTU/hr | 50/60 Hz | 100–240 V AC, autoranging |
| 1600 W AC | Platinum | 6000 BTU/hr | 50/60 Hz | 200–240 V AC, autoranging |
| 2000 W AC | Platinum | 7500 BTU/hr | 50/60 Hz | 200–240 V AC, autoranging |
NOTE: Heat dissipation is calculated by using the PSU wattage rating.
NOTE: This system is also designed to connect to the IT power systems with a phase to phase voltage not exceeding 230 V.
NOTE: PSUs rated for 1600 W and higher require high-line voltage (200-240 V) to supply their rated capacity.
System battery specifications
Expansion bus specifications
| Expansion card riser | PCIe slots on the riser | Height | Length | Link |
|---|---|---|---|---|
| Configuration 1 (System Config: D and G) | Slot 1 | half height | half Length | x16 |
| Slot 2 | half height | half Length | x16 | |
| Configuration 2 (System Config: A, B, and K) | Slot 1 | half height | half Length | x8 |
| Slot 2 | half height | half Length | x16 | |
| Configuration 3 (System Config: C, F, and H) | Slot 1 | half height | half Length | x8 |
| Slot 2 | half height | half Length | x8 | |
| Configuration 4 (System Config: E and I) | Slot 1 | half height | half Length | x8 |
| Slot 2 | NA | NA | NA |
Memory specifications
| Memory module sockets | Memory capacity | Minimum RAM | Maximum RAM |
|---|---|---|---|
| Sixteen 288-pin | 4 GB single rank, 8 GB, 16 GB, 32 GB dual rank, and 64 GB quad rank |
|
|
Drive specifications
NOTE: Systems with NVLink configurations do not support the 2.5-inch SAS/SATA cabled hard drives.
NOTE: Initial status LED of PCIe SSDs may vary based on the actual drive status and server components populated.
Ports and connectors specifications
| Connectors | ||
|---|---|---|
| Back | ||
| NIC | Two 1 Gbps | |
| Serial | 9-pin, DTE, 16550-compatible | |
| USB | Two 4-pin, USB 3.0-compliant | |
| Video | 15-pin VGA | |
| Internal | ||
| USB | One 4-pin, USB 3.0-compliant | |
| Internal dual SD module | Two optional flash memory
card slots with the internal dual SD module NOTE: One card slot is dedicated for redundancy. |
|
Video specifications
| Resolution | Refresh rate (Hz) | Color depth (bit) |
|---|---|---|
| 640 X 480 | 60, 70 | 8, 16, 32 |
| 800 X 600 | 60, 75, 85 | 8, 16, 32 |
| 1024 X 768 | 60, 75, 85 | 8, 16, 32 |
| 1152 X 864 | 60, 75, 85 | 8, 16, 32 |
| 1280 X 1024 | 60, 75 | 8, 16, 32 |
| 1440 X 900 | 60 | 8, 16, 32 |
Environmental specifications
NOTE: For additional information about environmental certifications, please refer to the Product Environmental Datasheet located with the Manuals & Documents on Dell.com/poweredgemanuals.
| Temperature | Specifications |
|---|---|
| Storage | –40°C to 65°C (–40°F to 149°F) |
| Continuous operation (for altitude less than 950 m or 3117 ft) | 10°C to 25°C (50°F to 77°F) with no direct sunlight on the equipment.
NOTE: Certain system configurations may require reductions in the upper temperature limits. NOTE: The performance of the system may be impacted when operating above the upper temperature limit or with a faulty fan. |
| Maximum temperature gradient (operating and storage) | 20°C/h (36°F/h) |
| Relative humidity | Specifications |
|---|---|
| Storage | 5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be non-condensing at all times. |
| Operating | 10% to 80% relative humidity with 29°C (84.2°F) maximum dew point. |
| Maximum vibration | Specifications |
|---|---|
| Operating | 0.26 Grms at 5 Hz to 350 Hz (all operation orientations). |
| Storage | 1.88 Grms at 10 Hz to 500 Hz for 15 min (all six sides tested). |
| Maximum vibration | Specifications |
|---|---|
| Operating | Six consecutively executed shock pulses in the positive and negative x, y, and z axes of 40 G for up to 2.3 ms. |
| Storage | Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of the system) of 71 G for up to 2 ms. |
| Maximum altitude | Specifications |
|---|---|
| Operating |
30482000 m (10,0006560 ft) |
| Storage | 12,000 m (39,370 ft) |
| Operating temperature de-rating | Specifications |
|---|---|
| Up to 25°C (77°F) | Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m (3,117 ft). |
| Particulate contamination specifications | |
|---|---|
|
NOTE: The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for you to re-mediate the environmental conditions that are causing the damage and/or failures. Re-mediation of environmental conditions will be the responsibility of the customer. |
|
| Air filtration
NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor. |
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
NOTE: Air entering the data center must have MERV11 or MERV13 filtration. |
| Conductive dust
NOTE: Applies to data center and non-data center environments. |
Air must be free of conductive dust, zinc whiskers, or other conductive particles. |
| Corrosive dust
NOTE: Applies to data center and non-data center environments. |
|
| Gaseous contamination specifications | ||
|---|---|---|
|
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity. |
||
| Copper coupon corrosion rate | <300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985. | |
| Silver coupon corrosion rate | <200 Å/month as defined by AHSRAE TC9.9. | |